When the connection is established correctly, the nE2 device extension will go from gray to green.
During the first connection to the device using a default password, a message will be displayed requesting to change the password.
Note: Changing password is obligatory when first connecting to the device!
Once properly connected, expand the nE2DeviceExt. A new tree component is visible.
The nE2DeviceExt structure Once expanded, the default available containers will appear in the device tree structure:
Note: The device icon will change from green to gray.
Warning: If the typed password is incorrect, a popup will appear. Repeat the previous step again and input the correct password.
Note: The default password must be changed after the first connection to the device in device platform
A new Tree component is visible.
The first connection with the device is fully established!
Note: To learn more about nano EDGE ENGINE architecture go to the nE2 Software Manual.
Upon connecting to the device in the emergency mode, the following notice pops up:
In the emergency mode, the device operation is limited:
libraries are not loaded;
the SD card configuration is not loaded;
only the System container with limited options (only Logs and Platform components) is displayed in the tree;
the ALM LED is lit continuously;
the iFnet runs with an IP/port taken from a flash storage;
Note: The flash storage must be synchronized to configuration slots when available.
no authorization or credentials are taken from the flash storage (like IP/port).
When the device enters the emergency mode, take one of a few possible actions:
read logs from the SD card if available;
reboot;
restore to defaults (using the Restore in the System context menu): remove files from the SD card (if available and formatted) excluding only files with IP, port, and credentials (libraries must be also removed);
restore to factory defaults (restoring with S1 6th DIP switch): format the SD card (if available), restore default credentials, IP, mask, gateway, iFnet port.
Copyright ©2025 iSMA CONTROLLI. All rights reserved.