This extension imports one or more remote Schedule and/or Calendar objects into a station as a read-only schedule component. You use these BACnet schedules or calendars in the station.
The BACnet property Priority for Writing is included, however, it means little in the station usage of this imported schedule.
In addition to the common properties (Status, Enabled and Fault Cause), this component has these properties.
| Property | Value | Description |
|---|---|---|
| State | read-only | Indicates the condition of the BACnet schedule. |
| Last Attempt | read-only | Indicates when the last attempt at an import was executed. |
| Last Success | read-only | Indicates the last time the station failed to perform this function. |
| Last Failure | read-only timestamp | Indicates the last time the station failed to perform this function. |
| Object Id | drop-down list and number (from 0 to 4194302) | Identifies each device and component by the type of entity (Object Id) combined with a unique Instance Number.
For devices (controllers, instruments, meters, etc.), |
| Priority for Writing | numeric text values 1 through 16 | Reports schedule priority, which defaults to 16. |
This extension has four control-time trigger properties: Execution Time (Interval, Manual, Daily), Trigger Mode, Last Trigger, and Next Trigger. These properties are documented in the Niagara Drivers Guide