If needed, change this by adding a maxOverrideDuration facet (choosing type baja:RelTime), with specified duration time, to either or both:



When a writable point is limited by a maxOverrideDuration facet, its action menu adjusts to show the allowable range.
The Sys Info property of the station’s root Config component has a facets control, shown in the Config component’s property sheet.



Adding this facet on the Sys Info property acts a global limit (station-wide) to a manual override action to all control points
that do not have their own maxOverrideDuration facet.
Each writable control point in the station can have a separately specified maximum override duration. If this facet is present,
it overrides any global (Sys Info) maxOverrideDuration value.



As shown, this maxOverrideDuration facet can be added along with any other facets in use by the control point. The example BooleanWritable point above already
had configured facets for trueText and falseText.
Example action menus from writable points with a maxOverrideDuration facet in effect are shown .
|
Global (Sys Info) level example |
Point level example |
||
|---|---|---|---|
<<<<<<< HEAD
<<<<<<< HEAD
![]() |
![]() ![]() |
![]() ![]() |
![]() |
If a system user attempts to invoke a Custom override over the specified maxOverrideDuration limit, an error window appears that shows the override duration range as shown below.



As shown above, the allowable duration range appears in [brackets], in this case [1ms - 1hour].