Alarm Console options include the following:
| Property | Value | Description |
|---|---|---|
| Notes Required on Ack | true or false (defaults to false)
|
Causes the Notes window to open whenever you initiate an alarm acknowledgement from the alarm console, if this option is set to true.
|
| Sounds Enabled | true or false (defaults to true)
|
Causes a sound to accompany an alarm. You can also set this value under the Alarms menu in the
|
| Default Sound File | file path | Sets the path to the default sound file. |
| Continuous Alarm | true or false (defaults to false)
|
Causes an alarm to repeat continually, until it is acknowledged or cleared, if this option is set to true. This option works together with the Continuous Alarm Delay property. You can also set this value under the Alarms menu in the
|
| Continuous Alarm Delay | hours, minutes, and seconds | When Continuous Alarm is enabled, this property causes a pause time between in the continuous alarm sound. The continuous alarm is interrupted
for a time equal to the value of this property.
|
| Alarm priority coloring | color | The following properties work together in combination to produce a range of colors that are assigned to the possible range
of alarm priorities (1 - 255).
|
| Time Zone Display | drop-down list (defaults to Console) | Allows you to choose to display alarm record timestamp values in the time zone of the alarm console view (Console) or in the time zone of the alarm source (Source). |
| Alarm Class Mapping | path | Provides a way for you to create alarm classes and map specific alarms to classes. |
| Alarm Ack Responses | text | Creates one or more text entries that you can use to displays the Notes window when acknowledging an alarm. When the Notes Required on Ack is set to true, the Notes window displays an additional option list containing any entries you create with this property. Use the button to open the
associated Edit window and add, edit, or remove response options, as desired. When the Notes Required On Ack is set to false, these Alarm Ack responses are not visible.
|
| View Instructions | true or false (defaults to false)
|
This property causes the alarm Instructions pane to display across the bottom of the Alarm Console, if this option is set to true.. Instructions display in the pane for any single selected alarm that has associated instructions.
|