obixDriver-ObixHistoryDeviceExt

This component discovers, adds, and manages history imports for the ObixClient and R2ObixClient. It manages the import of historical data from the oBIX server into the Niagara 4 history space. Use its default Obix History Manager view to add oBIX history importdescriptors.
Figure 6.   History device extension properties
Image

To access these properties expand ObixNetwork > ObixClient, right-click Histories and click Views > AX Property Sheet.

Property Value Description
Retry Trigger container Defines how many times the retry trigger automatically tries to execute a descriptor component following an unsuccessful attempt.

The retry action executes a retry on any descriptors whose status is in fault. This continues until successful execution occurs.

Trigger Mode drop-down list Determines when a TimeTrigger fires.

Interval fires a trigger each time the specified interval elapses. You would use it to fire the trigger several times per day (for example, every 5 minutes).

Daily fires the trigger at a specific time on selected days of the week, and includes a randomized interval so that the trigger does not fire at exactly the same time every day.

Manual requires a human to fire a trigger.

Last Trigger read-only Reports when (by displaying a timestamp) the last trigger fired.
Next Trigger read-only Reports when the trigger is scheduled to fire next.