The example client used in this procedure is the ProSys Simulation OPC UA Client. Many other third-party simulation OPC UA clients are available, which you can use to connect to an OPC UA server.
Status likely reports {ok}.
A second New window opens. It contains several properties.
Name or use the default name and click Save.
Opc Tcp Connection Address.Any OPC UA client attempting to connect to the server requires this connection address.
Opc Tcp Connection Address may be blocked by your PC/network firewall. The firewall settings may need to be adjusted to allow data transfer on this
port.
The OPC UA server set up is complete. For any OPC UA client connection to succeed, the client must be configured with the
server’s Opc Tcp Connection Address, as well as a Security Mode, Security Policy, and User Authentication method as required by the server.
Username and password values also must be defined in the station’s UserService.