Starting in AX-3.5, the Bacnet Device Manager provides a
button that lets you send a manual (one-time) time synchronization message, from the station to all BACnet devices on the
network.
Prior to AX-3.5, this function was available only from a BACnet Supervisor’s Bacnet Ws Device Manager view. This functionality was moved from the bacnetws module into the core bacnet module.
When you click
, you are first asked to confirm this action, as it will send the current station time to all controllers on the network.
If you choose , you see a Synchronize Time dialog, shown in Figure 27.
As shown above, this dialog has two fields:
Time Synch Type
Select either Local Time (default), or UTC Time.
Time Synch Range
Select either Local Networks Only (default), or All Connected Networks.
When you click OK, a time synchronization request is then broadcast to the network. This is a one-time message.
If you wish to schedule periodic BACnet time synchronization sent from the station, configure this in the LocalBacnet Device (AX-3.5 and later). See Time synchronization properties for details.
Such LocalDevice configuration also applies to a BACnet AWS Supervisor (BacnetAwsNetwork) or BACnet OWS Supervisor (BacnetOwsNetwork).
Copyright © 2000-2016 Tridium Inc. All rights reserved.