Below is an example Edit dialog for a ZWave proxy point. To edit a point, double-click it in the ZWave Point Manager, or select one or more points and click the button.
Change values as needed, using the guidelines below.
Name
If desired, type in to replace the default Z-Wave proxy point name, where each name must be unique in the parent container for the proxy point.
Type
Cannot edit (type is ZWaveProxy or ZWaveThermostatSetPointProxy).
Enabled
Accept the default “true” (if set to “false” point status is set to disabled, and the item is not polled).
Facets
Edit as needed for proper unit display and decimal handling of the selected item. If a numeric writable, a min or max (other than defaults -inf and +inf) may be desired to limit what can be entered from an override or set action.
ZWave proxy points typically have an appropriate unit preselected, based on command class.
Tuning Policy Name
Accept the standard “Default Policy”, or if additional tuning policies have been added to the ZWaveNetwork, select another tuning policy if needed. If this is point is in a FLiRS device, (Frequently Listening Routing Slave) the tuning policy will set to “flirsPolicy”by default.
Device Facets
Accept defaults—usage is not applicable in ZWave driver.
Conversion
Typically, the “Default” conversion is the only useful conversion selection.
In the case of a Z-Wave proxy point based on a BooleanPoint or BooleanWritable, where you need to “flip” the output logic, you can select the conversion type Reverse Polarity.