You can create a report Px page using bound labels and bound tables to display real time data. Bound tables can also be used to display historical data on the reports as well.
A bql query can be entered in the ord field of the bound label binding (see Figure 1), as opposed to referencing a component in the station. Animating the text field allows displaying the results of the bql query. If the bformat text is configured to '%.%' then it will simply display the value. Additional standard text may be used as well such as, 'Points With Alarms Disabled (Alarm Inhibit = True): %.%'.
The bql query is entered in the ord field of the bound table to display the list of points or historical data (see Figure 2).