Properties of the ProvisioningNwExt (Figure 18) are described as follows:
Status — Is either fault if provisioning is not licensed, disabled if Enabled property is false, and in all other cases is ok.
Enabled — If set to false, provisioning activity cannot occur, and provisioning-related extensions in NiagaraStations are set to disabled.
Fault Cause — Text explanation for why the extension is in fault.
Four container components (see next section ProvisioningNwExt container components).
Device Reboot Timeout — Specifies the maximum time in seconds that a provisioning job step will wait while attempting to reconnect to a station that has been rebooted before setting the step status to “failed”, and advancing to the next station. The default time is 600 seconds (10 minutes).
Station Shutdown Timeout — Specifies the maximum time in seconds that a provisioning job step will wait for a station to stop after receiving a shutdown request before setting the step status to “failed”, and advancing to the next station. The default time is 180 seconds (3 minutes).