When shipped, a new RB-603 or RB-645 retrofit board is pre-configured with an IP address (IPv4) as:
192.168.1.12n (primary “LAN1” port, the “LAN2” port is disabled)
where the last numeral (n) in the IP address matches the last numeral in the JACE’s serial number.
In all cases, the default subnet mask is: 255.255.255.0
You change these IPv4 network settings during your startup commissioning of the JACE.
When shipped, the platform daemon of a a new RB-603 or RB-645 retrofit board is configured to listen on HTTP port 3011. Often, this is left at default. However, if a different port is needed for a platform connection (perhaps for firewall reasons), you can change this during the commissioning of the JACE.
Like any JACE controller, a new RB-603 or RB-645 retrofit board is shipped with these platform daemon (administrator) credentials:
Username: tridium Password: niagara
Initially, you use these default credentials to open (login) a platform connection to the JACE. Like the factory-assigned IP address, default credentials are intended to be temporary. During your startup commissioning, you should change these credentials to be something unique, and guard them closely.