nrio-Nrio16PointManager

Use the Nrio16 Point Manager to add, edit, and access Nrio proxy points under the Nrio16Points extension of a selected Nrio16Module (or points extension of any NrioModule), or in an Nrio16PointFolder. The Nrio16 Point Manager is the default view on both types of these components. To view, right-click the Nrio16Points extension or NrioPointFolder and select Views->Nrio Point Manager, or simply double-click the component.

Columns in the Discovered and Database panes of this view are summarized below. For more details, see Nrio Point Manager.

Discovered

The Discovered pane of this view has the following available columns:

  • Name

    Shows a default name for each available IO point, using format “AbbrevIoTypeTerminalNumber”, for example, “ui4”, “ao2”, and so on.

  • Io Type

    Type of I/O for each point, such as Universal Input, Relay Output, or Analog Output.

  • Instance

    Equals the hardware I/O terminal number for that IO type, for example “1” for UI 1 or AO 1.

  • Used By

    Has a value only if the IO point is already represented in the station’s database, formatted as ParentName.NrioProxyPointName. For example, Onboard_IO.AHU_status or Inputs1.ReturnAir

    NoteTo see the complete ord for the associated proxy point, right-click and select “Show Existing”.

Database

The Database pane of this view has the following available columns:

  • Name

    Component name of the Nrio proxy point.

  • Type

    Base NiagaraAX control point type, such as BooleanPoint, NumericPoint, NumericWritable.

  • Instance

    Equals the hardware I/O terminal number for that IO type, for example “1” for UI 1 or AO 1.

  • Ui Type

    Descriptor for type of UI (if applicable), blank if point is an AO or DO. For example, DI_Normal, AI_Resistive, AI_0to10_Vdc, DI_High Speed, and so on.

  • Conversion

    Conversion type used in Nrio ProxyExt, such as Linear, Default, 500 Ohm Shunt, Thermistor Type3, and so on.

  • Value

    Current out value and status of proxy point.

  • Facets

    Facets information string for proxy point, including units, precision, and min/max value for numeric points, or true/falseText for boolean points.