EnumCommandFailureAlarmExt implements command failure alarm detection algorithm for enum objects as described in BACnet.
If feedback and output values of the enum point are not equal for more than timeDelay, an offnormal alarm is generated. This
alarm extension is available in the Extensions folder of the alarm palette.
See the following links for more information:
Copyright © 2000-2016 Tridium Inc. All rights reserved.