(AX-3.5 only) After adding a WeatherReport using the NwsWeatherProvider, you may wish to review the default settings for handling National Weather Service advisories.
Configuring advisory alarming (AX-3.5 only)
With the station opened in Workbench:
In the Nav tree, expand the WeatherReport’s
Provider to reveal its
Advisories Alarm Ext.
Double-click the Advisories Alarm Ext for its property sheet.
By default, NWS advisory alarming is enabled. If you wish no NWS advisories (essentially pre-AX-3.5 operation), set the Enabled
property to false, and click . Skip the remaining steps.
Review and possibly change the “Urgency” property setting, from the default “Immediate” to another setting, shown in the selection list ordered highest priority at top, to lowest at bottom.
For example, select “Expected” to include advisories with that urgency level, along with “Immediate”, but to filter out advisories with urgency levels “Future”, “Past”, and “Unknown”. This may include “warnings” but filter out “watches”.
Expand the
Alarm Properties (Alarm Source Info) container and specify the alarm class to use in the station for alarms from this WeatherReport.
The “Default Alarm Class” is used by default. However, typically you create one or more alarm classes to use for WeatherReport
advisory alarms, and specify one of these here.
Remaining properties are optional and often left at defaults. Click when finished.
For further details, see the following sections: