NOTE: The system passphrase default value is the same as the default platform password for controllers that you have just converted
from
NiagaraAX, and controllers on which you have just installed a clean dist. On the first commissioning of such controllers you are prompted
to change the passphrase from the default value.
When inserting a JACE-8000 SD card into a replacement unit, note the following:
- If the replacement unit is preconfigured with the same system passphrase, the unit starts.
- If the replacement unit has a different system passphrase, the unit will not boot, and the status LED flashes every second.
To resolve, you must make a serial connection and, when prompted, select either: Update the system passphrase, or Remove all encrypted data.