Modules step

 
NOTE: This wizard step is skipped if a station backup, or if all modules required by the station to be installed are already in the JACE controller. In this case, you see either the “Stop station step” or “Review step” instead.
 

This step occurs if the target JACE platform is missing one or more of the modules required by the station being copied (installed). It lists the missing modules/versions that will be installed during the station copy operation. If included, this is the final step before the station copy process starts.

 
NOTE: Dependencies of the missing modules are compared against the software that is already installed in the target JACE platform. The Station Copier looks for versions of those missing modules in your Workbench software database that can be installed without re-commissioning the JACE, by default.
 

There are two possible results when the wizard reaches this step:

In either case, to continue you click either:

  • Finish — Start the local-to-remote copy, including installation of the listed modules. Progress updates appear in a “Transferring station” dialog.
  • Cancel — Exit from the Station Transfer Wizard, then either select another station to install, or if a JACE upgrade is possible (and you have purchased an upgrade license for it) run the Commissioning Wizard to upgrade the JACE controller, including the installation of a station.