CVAHU

Description

The W7750 series is the Constant Volume Air Handling Unit (CVAHU) controller in the Excel 10 family. It is a LonMark compliant device designed to control single zone and heat pump air handlers. The W7750 series can be configured to control a wide variety of possible equipment arrangements (see Common Configuration Options Summary for CVAHU). The various model for The XL10 CVAHU is available as follows.

Links

Purpose

To configure a CVAHU application.

Navigating to CVAHU Pages

Learn how to navigate to the CVAHU pages.

Fields

Criteria W7750A W7750B W7750C W7750B Enhanced
Digital Outputs 6 (Relay) 8 5 8
Analog Outputs 0 0 3 0
Conventional or Heat pump control yes yes yes yes
Stages of electric or gas fired heating 1-4 1-4 1-4 1-4
Stages of Cooling 1-4 1-4 1-4 1-4
Heating N/A Floating, or Pulse width modulated Floating, Pulse width modulated, reverse Pulse width modulated, Analog, or reverse Analog Floating, Pulse width modulated, reverse Pulse width modulated
Cooling N/A Floating, or Pulse width modulated Floating, Pulse width modulated, Reverse Pulse width modulated, Analog, reverse Analog Floating, Pulse width modulated, Reverse Pulse width modulated
Mixed Air Damper Output Floating Floating or Pulse width modulated Floating, Pulse width modulated, Reverse Pulse Width modulated, Analog, reverse Analog Floating, Pulse width modulated, Reverse Pulse Width modulated
Optional outputs AuxEcon, OccStatus, Free1, Free2, Free1PulseOn or Free1PulseOff AuxEcon, OccStatus, Free1, Free2, Free1PulseOn or Free1PulseOff AuxEcon, OccStatus, Free1or reverse Free1, Free2 or Reverse Free2, Free1PulseOn or Free1PulseOff
Free1AO or Free1AORev
Free2AO or Free2AORev
AuxEcon, OccStatus, Free1or reverse Free1, Free2 or Reverse Free2, Free1PulseOn or Free1PulseOff
Override Occupancy sensor override and window open override Occupancy sensor override and window open override Occupancy sensor override and window open override Occupancy sensor override and window open override
Analog Inputs 3 resistive 4 resistive and 2 voltage 4 resistive and 2 voltage
With Outdoor 20KNTC sensor support
4 resistive and 2 voltage
With Outdoor 20KNTC sensor support
Digital Inputs 3 digital inputs 5 digital inputs 5 digital inputs with Coil Freeze Status support 5 digital inputs with Coil Freeze Status support
LED digital output Yes Yes Yes Yes
Power Supply N/A 22 VDC power supply 22 VDC power supply 22 VDC power supply

Note: One digital input is reserved for the Wall Module Bypass.

One analog input reserved for Wall Module Sensor and one analog input reserved for Wall Module Setpoint.

Consult the System Engineering Guide before configuring the CVAHU. Also, refer to Excel 10 W7750A,B,Enhanced B, C Constant Volume AHU Controller Specification Data, form 74-2956; or Excel 10 W7750A, B,Enhanced B, C Constant Volume AHU Controller Installation Instructions, form 95-7521-1 for more information.