Use the Unit Ventilator Zone Options page to set heating and cooling setpoints.
Enter all outputs, including optional outputs, to be controlled by the Unit Ventilator Controller.
Off-line or On-line
| Name | Definition |
| Cooling Occupied Setpoint | Enter Occupied cooling setpoint (range: 50 deg.F to 95 deg.F [10 deg.C through 35 deg.C]). |
| Cooling Standby Setpoint | Enter Standby cooling setpoint (range: 50 deg.F to 90 deg.F [10 deg.C through 32 deg.C]). |
| Cooling Unoccupied Setpoint | Enter Unoccupied cooling setpoint (range: 50 deg.F to 90 deg.F [10 deg.C through 32 deg.C]). |
| Heating Occupied Setpoint | Enter Occupied heating setpoint (range: 50 deg.F to 90 deg.F [10 deg.C through 32 deg.C]). |
| Heating Standby Setpoint | Enter Standby heating setpoint (range: 50 deg.F to 90 deg.F [10 deg.C through 32 deg.C]). |
| Heating Unoccupied Setpoint | Enter Unoccupied heating setpoint (range: 50 deg.F to 90 deg.F [10 deg.C through 32 deg.C]) |
| Use Wall Module Setpoint | Select usage of setpoint adjustment potentiometer on a connected Wall Module. This field is active is you selected a Sensor_Setpoint type in the Wall Module field on the Input tab. |
| Min. Limit Setpoint | Provides a lower limit on the allowed settings of the Wall Modules setpoint knob. Enabled if Use Wall Module Setpoint is Yes. Values range from 55 deg.F to 85 deg.F when the setpoint knob type is absolute and range for relative setpoint knob type is 9 to 9 DDf |
| Max. Limit Setpoint | Provides an upper limit on the allowed settings of the Wall Modules setpoint knob. Enabled if Use Wall Module Setpoint is Yes. Values range from 55 deg.F to 85 deg.F when the setpoint knob type is absolute and range for relative setpoint knob type is 9 to 9 DDf |