There are 8 Start Stop Loops in the XL15C Plant Controller.
Start stop loops are used to turn equipment on and off based on a schedule (TOD) or Demand situation (DLC). Minimum on/off times are observed. The start stop control loops are open loop control driven essentially by the occupancy arbitration effective occupancy. Since the start stop control loops have only a command digital output, it's output value is on or off. The start stop configuration is used to set up the control loop's input and output choices.
Configure upto eight start stop loops.
Off-line or On-line.
- Min On Time
- Min Off Time
- Bypass Time
| Name | Definition |
| Override Priority | Defines the occupancy arbitration of the Start/Stop Loop. It can be Network Wins or Last One Wins. This field plays a role when the Loop comes out of Bypass mode to Normal mode. |
| Min On Time | Defines the minimum on time of the Start/Stop loop. It means if the loop changes to on from off state, it should be on at least for this amount of time. The unit is minute. The default value of this field is 0 and range is 0 to 254. |
| Min Off Time | Defines the minimum off time of the Start/Stop loop. It means if the loop changes to off from on state, it should be off at least for this amount of time. The unit is minute. The default value of this field is 0 and range is 0 to 254. |
| Bypass Time | This field defines Start/Stop loop Bypass Time. If the loop is set to Bypass mode, it remains in that mode depending on value set in this field. The unit of is minute. The default value of this field is 0 and range is 0 to 1080. |