The XL15C controller has 8 Digital Inputs.
Digital Inputs are used to monitor external events, such as contact closures (10 mA, 5Vdc). The contact closures initiate alarms, monitor equipment status, and read pulse meters. These inputs are commonly used as inputs to Control Loops, Start /Stop Loops, Math Functions & Logic Loops.
Each Digital Input can be configured as Maintained, Momentary, Counter Slow, Counter Fast, Pulse Meter.
An external digital input source is connected to the digital input.
Specify the sensor types and attributes for up to eight digital inputs.
Off-line or On-line.
Limits
Two digital inputs can be configured as counters. A counter counts the number of active inputs within the range of 1 through 65,535. Pulse No. 65,536 automatically resets the counter to 0.
| Name | Definition |
| Input Kind | The input kind can be one of the following types:
|
| Engineering Units | The Engineering Unit list contains all the engineering units you can assign to a digital input. Engineering Unit is enabled only for Input Kind of Maintained and Momentary. |
| Digital Configuration | State The state option has 2 choices: Normally Open and Normally Closed. By default, normally open is selected. Normally open = Off when the input contact is open and On when closed. Normally closed = Off when the input contact is closed and On when open. Type The type option has 2 choices: Unconfigured and Sensor occupancy. The type option is enabled only for Input Kind of Maintained and Momentary and disabled for all others. |
| Pulsemeter | Scale Factor The scale factor is enabled only when the Input Kind selected is Pulsemeter. The scale factor has a range of 0 1000 KWHR/pulse. |