XL15C Configuration
Configuring Excel 15C DigFreeCmd
The DigFreeCmd object is used to connect a digital output of an internal object like
flex loop's staged output / logic loop's OR output to an external device in the network.
Procedure
- Drag a DigFreeCmd object from the palette and drop it on the wiresheet.
- Create a link from any of the internal objects like Logic Loop.
- The wiresheet opens up a Link dialog.
- Select the source slot (for eg. Or Out Link) and select the destination slot on the
DigFreeCmd object (for eg. Command Link).
- To link the DigFreeCmd to an external object, right click on the DigFreeCmd object and
select the "Link Mark" option.
- In the Navigation tree, right click on a device under LonNetwork and select the
option "Link From DigFreeCmd".
- This will bring up a "Link" dialog. Select the source slot - "Nvo
Dig Cmd Free" and select any appropriate slot on the destination device.
- This will create LON bindings. The LON bindings can be viewed from the "Lon
Link Manager" view of LonNetwork.
- Remember to select the bindings from this view and select "Bind"
/ "Selective Bind" option. Selecting this option downloads the
bindings to the device.
Note
Any change in the configuration needs to be downloaded to the controller. Until then,
the objects would be marked as "Stale".This is an indication that these changes
need to be downloaded to the controller.Invoke "Download" to download the
configuration changes to the controller.