Use the Flow Pickup Table page to configure VAV Flow pickup settings.
Specify differential pressure and velocity for flow sensors. Define the differential pressures and velocities for the flow sensors. These values would be used to calculate the flow linearization values during the download sequence.
Configuration can be performed with the device On-line or Off-line.
| Name | Definition |
| Pt 1 through Pt 10 | Ten pairs of airflow values (Inw [Differential pressure] and FPM [velocity]) |
| Flow Sensor Type | List of tables that contains manufacturers' specifications for airflow units. Each table has 10 pairs of airflow values versus feet per minute or feet per second. When a sensor is selected from the table, the airflow values are set to the default specific to the chosen sensor. |
| Edit Column | This list has Velocity and Volume options. You can select Velocity, change the velocity value and select Yes in Update Alternate Column to update the volume values. Alternatively, you can modify the volume values and update the velocity. |
| Update Alternate Column | You can choose:
|