VAV II Diagnostics

Excel 10 VAV II Diagnostics

Use the RIO page to configure RIO inputs.

Purpose

After configuration and commissioning, the controller is put into test mode and checked out for proper operation.

CAUTION

Equipment Damage Possible.

May cause short-cycling of compressors, or cause damage to other heating or cooling equipment.

You must take appropriate and recommended precautions when initiating the Test Mode. This mode directly drives controller outputs to the manually-entered states.

Place the controller in manual mode. In this mode, the controller’s application goes off-line and you can view and command the outputs within the context of the application schematic.

Mode

On-line.

Procedure

  1. Click the Inputs button on the left pane to open the RIO's Inputs Configuration Page.
  2. Enter information into available fields.
  3. Click Commit to save the settings or Reset to revert to the last saved settings.
  4. Click Next to display the RIO's H/C Stage Parameters Configuration Page or Back to display the Unit Vent's Equipment Control Configuration Page.
  5. The diagnostic screen for VAV II displays the configured digital outputs. The current sensor values are also displayed.

Fields

Name Definition
Inputs The values of configured digital and analog inputs are displayed.
Outputs The analog and digital outputs that can be commanded are also displayed. The user can drive the values of these outputs.

Back