Use the KeyPd/Display page to configure the keypad lockout level, display temperature
unit in the thermostat, time display format, system switch configuration and fan switch
configuration.
Off-line or On-line.
| Name |
Definition |
| KeyPad Lockout |
Use this option to configure the keypad lockout enable/disable through
special keypad sequence on the thermostat.
- Enable All: Selecting this option will allow the user to access any
keys on the thermostat. No lockout will be imposed.
- Enable Setpoints & Override: This option will lockout all keys
except Temperory Occupied, Temporary Not Occupied, increase and decrease and information
key.
- Info Key Only: This option will lockout all keys information key
|
| Display Units |
Use this option to configure the display units in the thermostat for
temperature fields.
- Degrees F: Select this option to set the display unit for temperature
fields as degree Fahrenheit.
- Degrees C: Select this option to set the display unit for temperature
fields as degree Centigrade.
|
| Clock Display |
Use this to configure the display mode of time in the thermostat.
- 12 Hour(AM/PM): Selecting this option will display the thermostat time
in 12 hour format.
- 24 Hour: Selecting this option will display the thermostat time in 24
hour format
|
| System Switch |
Use this option to configure the system operation of the thermostat.
- OFF: When this option is selected, heat and cool states are disabled.
- AUTO: The thermostat is configured for Automatic Changeover. When this
option is selected, heating and cooling stages are enabled to maintain heating and cooling
setpoints.
- Cool: When this option is selected, cooling stage operates on call for
cooling. Heating stages are disabled.
- Heat: When this option is selected, heating stage operates on call for
heating. Cooling stages are disabled.
- Emergency Heat: This option is available only when the equipment type
is selected as Heat Pump. Auxiliary heat serves as stage one. Compressor stages are locked
off.
|
| Fan Switch |
Use this option to select the fan switch.
- On (On in occupied): When this option is selected, fan operates
continuously in scheduled occupied and stand by periods and bypass mode. Fan cycles with
call for heating or cooling during unoccupied periods.
- Auto (Intermittent in Occupied): When this option is selected, fan
cycles with call for heating or cooling during scheduled occupied, standby and unoccupied
periods.
Note: If the T7350 is scheduled for occupied and occupancy sensor is
unoccupied(thus effective occupancy is standby), then the fan is off and will turn on with
a call for heating and cooling. This applies to both On and Auto.
This follows the action of the auxiliary relay when configured for TOD.
This is further modified by the selection of conventional(OFF with Heat) or electric heat
(ON with Heat). |