Use the General page to configure the thermostat model, equipment type, outputs, inputs, day light savings details.
Off-line or On-line.
| Name | Definition | ||||
| Thermostat Model | The T7350 Communicating Subbase(T7350CS) comes in two models, T7350H1009 and T7350H1017. T7350H1009: This subbase is the Three Heat/Three Cool model. It allows for conventional or heat pump operation. A total of 8 relays are available with the thermostat cover assembly and subbase. The auxiliary relay may be configured for an economizer, TOD, or dehumidification. The subbase may be configured for 3 Heat/ 3 Cool or 2 Heat/ 4 Cool by using the third stage of heat for an additional stage of cooling. T7350H1017: This subbase is the modulating subbase. A total of 4 relays are available with the thermostat cover assembly and subbase. The auxiliary relay may be configured for an economizer, TOD, dehumidification or an additional stage of heating and cooling. See the section on Outputs for description on these relays. |
||||
| Equipment Type | This field specifies the operation in which this subbase is used. When the thermostat model is selected as T7350H1009, the equipment type can be selected as Standard or Heat Pump. The T7350H1009 subbase allows for conventional or heat pump operation. When the model is selected as T7350H1017, the equipment type is changed to Standard and this option is disabled for selection. When the T7350H1017 model type is selected, the Heat Action and Cool Action options under Outputs are enabled for selection. The modulating subbase does not allow for heat pumps. |
||||
| Inputs | This section allows the user to configure the inputs to the thermostat | ||||
| Room Temp | This option allows the user to configure the source of room temperature input to the thermostat. The T7350 thermostat is equipped with its own internal room temperature sensor. The sensor operating range is 30 deg F to 110 deg F. The T7350 thermostat is compatible with the following Honeywell Wall Modules:
Options available are
Note 1: Open, short or out-of-range on the internal or remote room temperature sensor input(s) to the thermostat will cause the outputs to be turned off. The fault detection is done only on the sensor being used. That is, if the internal(local) sensor is being used, faults on the remote sensor are ignored. |
||||
| Room Humidity | Use this option to configure the source of room humidity input to the thermostat. Options available are:
|
||||
| Discharge Air Temp | Use this field to configure the source for discharge air temperature input. The following options are available:
|
||||
| Outdoor Air Temp | Use this field to configure the source for outdoor air temperature input. The following options are available:
|
||||
| Occupancy Sensor | Use this field to configure the source for occupancy input. The following options are available:
|
||||
| Daylight Savings | Use this option to configure the settings for daylight savings. The following describes each field: Enable Daylight Savings: This option is enabled by default. Disable this option if the daylight savings feature is not required to be followed by the thermostat. Unselecting this option will disable the Start Month, Stop Month, Start Day and Stop Day fields. Start Month: This field is available for configuration only if the Enable Daylight Savings option field is selected. Its default value is April. Change this option according to the daylight savings settings in the country where the thermostat is installed. Start Day: This field is available for configuration only if the Enable Daylight Savings option field is selected. Its default value is First Sunday. Change this option according to the daylight savings settings in the country where the thermostat is installed. End Month: This field is available for configuration only if the Enable Daylight Savings option is selected. Its default value is October. Change this option according to the daylight savings settings in the country where the thermostat is installed. Start Day: This field is available for configuration only if the Enable Daylight Savings option is selected. Its default value is Last Sunday. Change this option according to the daylight savings settings in the country where the thermostat is installed. |
||||
| Configuration ID | When you click this button, the button label is replaced by a 16 character alphanumeric number/code with every 2 digits separated by a period. This code represents the configuration information that define the equipment that is connected to the thermostat. This code can be entered through the thermostat keypad using the installer configuration ( press Run/Copy buttons simultaneously and navigate to the code. You are presented with a number identified by C1. Enter the first 2 digits of the configuration ID that the wizard has generated. Continue entering 2 digits each for C2 to C8. Save this code using Run button). The configuration in the thermostat is changed to that in the wizard. The thermostat installer set up allows the user to enter the configuration through the keypad. When the 'Configuration ID' button is pressed the wizard derives the configuration string that user can enter into the thermostat through keypad. This way, the configuration in thermostat is same as it is the wizard with respect to inputs, outputs, setpoints, loop tuning parameters, energy management parameters, bypass time. | ||||
| Outputs | Use this section to configure outputs. | ||||
| Heat/Cool Stages | Use these fields to configure the number of heat stages and cool stages for the application the subbase is being used for. | ||||
| Outputs | Model | Equipment Type | Default Value | Number of Stages Available for Configuration | |
| Heat Stages | T7350H1009 | Standard | Three Stage |
|
|
| T7350H1017 | Standard | Heat Enable |
|
||
| Aux Heat Stages | T7350H1009 |
Heat Pump | One Stage |
|
|
| Cool Stages | T7350H1009 | Standard | Three Stage |
|
|
| T7350H1017 | Standard | Cool Enable |
|
||
| Compressor Stages | T7350H1009 |
Heat Pump | Two Stage |
|
|
| When the model is selected as T7350H1009 and the equipment
type as Standard, the tool allows to configure for up to three stages of heating and three
stages of cooling. The fourth stage of cooling is available for selection as long as the
0/1/2 heat stages are selected. When the fourth stage of cooling is selected, the third
stage of heating is no longer available. When the model is selected as T7350H1009 and the equipment type is selected as Heat Pump, you will have option to configure for 0/1/2 auxiliary heating stages and 0/1/2 compressor stages. One relay is used for heat pump reversing valve. When the model is selected as T7350H1017, you can configure for 0/1/2 heat or cool stages. The modulating outputs are always active. They are always being driven 0-100%. When the number of stages is 0, the relay outputs are used to enable the heating or cooling outputs. Staged action may be used in addition to the modulating outputs. The number of stages is set to 1 or 2. It is not possible to have both 2 stages of heating and cooling. Examples: Example 1: Selecting heating stages and cooling stages as 1 configures for modulating heat and modulating cool action. Example 2: To have Mod heat, heating pump enable relay and 1 stage of heating, configure Heat Stages as Heat Enable, Heat Action (depends on the actuator connected) and connect the relay W1 such that it turns the heating pump ON or OFF. |
|||||
| Aux DO | Use this option to configure the auxiliary outputs. The auxiliary DO can be configured for econimizer, Time Of Day or for dehumidification. The dehumidification options available are Simple dehumid or Dehumid Hotgas BP. In the case of T7350H1017 model type, the auxiliary DO can be configured for second stage of heating or cooling. In that case, it cannot be configured for the above mentioned purposes and hence the option is disabled in the screen. Note: The dehumid options (Simple dehumid or Dehumid Hotgas BP) are available for configuration only if a humidity sensor is configured. |
||||
| Heat Pump Rev Value | This option is available for T7350H1009 model when the Equipment
Type is selected as Heat Pump. The options available are:
Select Active Cooling when the O/B valve is energized on cooling or Active Heating if the O/B valve is energized on heating. If the standard application is configured, this option is not available. |
||||
| Heat Action | This option is available for model is configured as T7350H1017 only. This is disabled when the model is selected as T7350H1009. This is applicable for modulating heat output, that is when the Heat Stages option is configured as Heat Enable. Select Direct 4-20mA if the actuator connected for heating action is driven from 0-100% and Reverse 20-4mA if is driven from 100-0%. | ||||
| Cool Action | This option is available for model is configured as T7350H1017 only. This is disabled when the model is selected as T7350H1009. This is applicable for modulating cool output, that is, when the Cool Stages option is configured as Cool Enable. Select Direct 4-20mA if the actuator connected for cooling action is driven from 0-100% and Reverse 20-4mA if is driven from 100-0% | ||||