Use the Equip Control page to configure the heating and cooling selections and loop tuning parameters.
Off-line or On-line.
| Name | Definition |
| Heating Selections |
This field specifies the selection of fan operation
The equipment (i.e. plenum switch) controls the fan operation in heat mode. The thermostat controls the fan operation in cool mode.
The thermostat controls the fan operation in both heat and cool modes.
Use this option to configure the time for extended fan operation after heating turns off. The choices are No Extend Op(0) or Extend 90 sec( 90 sec).
Use this option to configure the heating cycling option for standard or fast response systems. Available choices are: Slow 3 cph (standard response), Med 6 cph (medium), Fast 9 cph (fast), and Fast!! 20 cph (super fast).
This option is enabled only if the outdoor air temperature input is configured in the General page. This enables the heating lockout based on the outdoor air temperature.
This option is available only if the outdoor air temperature input is configured in the General page and Enable Heating OAT Lockout is selected. If outdoor air temperature is greater than Heat Lockout Setpoint then the heating is locked out.
This option is enabled only if the discharge air temperature input is configured in the General page. This will enable the usage of the discharge air high limit.
This option is available only if the discharge air temperature input is configured in the General page and Enable Heating DAT Hi Limit is selected. |
| Cooling Selections |
Use this option to configure the time for extended fan operation after cooling turns off. The choices are No Extend Op or Extend 40 sec.
This option allows the user to configure the cooling cycling option for standard or fast response systems. Available choices are: Std 3 cph (standard response), Fast 4 cph ( fast).
This option is enabled only if the outdoor air temperature input is configured in the General page. This will enable the cooling lockout based on the outdoor air temperature.
This option is available only if the outdoor air temperature input is configured in the General page and Enable Cooling OAT Lockout is selected. If outdoor air temperature is less than the Cooling OAT Lockout setpoint then cooling is locked out.
This option is enabled only if the discharge air temperature input is configured in the General page. This enables the usage of discharge air low limit.
This option is available only if the discharge air temperature input is configured in the General page and Enable Cooling DAT Low Limit is selected. |
| Loop Tuning | This section allows the user to configure the loop tuning parameters.
Use this screen to configure the heat and cool throttling ranges. The wizard automatically modifies the heat and cool throttling ranges when the number of stages configured is changed. For a conventional RTU:
For a heat pump RTU:
Throttling range remains always at 5 for T7350H1017 . If you change the number of stages to zero, the throttling range remains unchanged. The heat and cool throttling range values are selectable from 1-30 deg F(1-17 deg C). When you enter some invalid values, the wizard automatically modifies it to nearest valid value.
Use this to configure the heat and cool integral time values. The wizard automatically modifies the heat and cool throttling ranges when the number of stages configured is changed. Refer the following table for the default values of integral time values for different stages. Integral time remains always at 1250 for T7350H1017. A value of 0 means that the integral time is disabled.
Use this to configure the heat and cool derivative time for PID loop tuning. The value is selectable from 10 to 3000 seconds. 0 also is a valid value. A value of 0 means derivative time is disabled. If you enter any invalid values, the wizard automatically modifies it to nearest valid value.
Configure the anticipator authority value. You can enter a value between 2 15.
The default value is 4. |
| Heat/Cool Stages | 1 | 2 | 3 | 4 |
| Default Throttling Range | 3 | 4 | 7 | 8 |
| Default Integral Time | 3100 | 2500 | 1650 | 1250 |