RIO Deltas
Configuring RIO Deltas
Use the RIO Deltas page to configure RIO Deltas settings.
Purpose
Delta is an adjustable threshold that allows the user to determine, on a per-sensor
basis, what change in value is required before the sensor is updated. All Excel 10
controllers have a guaranteed periodic update time of 55 seconds, which requires that all
sensors report any change every update period. The delta for each sensor is used to reduce
LonWorks Bus traffic by reducing the amount of updates on a sensor that are constantly or
quickly changing. View or modify Deltas (change thresholds) for sensors.
Mode
Off-line or On-line
Procedure
- Click the Deltas_pane button on the left pane to open the RIO's Deltas Configuration
page.
- Enter information into available fields.
- Click Commit to save the settings or Reset to revert to the last saved settings.
- If sensors are being used for display only, then they can have a larger value for the
delta and rely on the guaranteed periodic update to update the sensor every 55 seconds
regardless on the amount of change.
- If the sensor is bound to another Excel 10 controller, configure a smaller delta so that
the control algorithm does not see large changes in value.
- The default value of 0 sends an update every 2 seconds.
- Click Back to display the RIO's Input Confguration page.
Fields
| Name |
Definition |
| Delta T1 |
Deg F |
| Delta T2 |
Deg F |
| Delta T3 |
Deg F |
| Delta T4 |
Deg F |
| Delta H |
Percentage |
| Delta P |
Inch H2O |
| Delta V |
Volts |
| Delta C |
Milliamps |
| Delta CO2 |
CO2lev |