Outputs

Configuring Unit Ventilator Outputs

Use the Unit Ventilator Outputs page to select outputs of heating and cooling stages. The outputs could be of stages, PWM, or floating types. In addition, the number of fan speeds and Economizer types must be set. You can also select optional points.

Purpose

Select all outputs, including optional outputs, to be controlled by the Unit Ventilator Controller.

Mode

Off-line or On-line

Procedure

  1. Click the UVOutputPane button on the left pane to open the Output Configuration page.
  2. Enter information into available fields.
  3. Click Commit to save the settings or Reset to revert to the last saved settings.
  4. Click Next to open the Input Configuration page.

Fields

Name Definition
Fan Speeds Select one of the following fan speeds:
  • No_Fan
  • One_Speed
  • Two_Speed
  • Three_Speed
Heating Select one of the following Heating types:
  • Heating_Stage_1
  • Heating_Stage_2
  • Heating_PWM
  • Heating_Floating
  • No_Heating

If you select Floating, the Motor Speed field displays actuator speed in seconds.

If you select PWM, the PWM Settings become editable.

Cooling Select one of the following Cooling types:
  • Cooling_Stage_1
  • Cooling_Stage_2
  • Cooling_PWM
  • Cooling_Floating
  • No_Cooling

If you select Floating, the Motor Speed field displays actuator speed in seconds.

If you select PWM, the PWM Settings fields become editable.

Economizer Selection of Economizer mixed air damper actuator type: None (or packaged external economizer), PWM, or Floating.
  • Econo_None_Pkgd
  • Econo_PWM
  • Econo_Floating

Note: If you configure a floating or PWM economizer, you MUST select a Discharge Air sensor (see Unit Ventilator Inputs) to enable automatic damper control.

Motor Speed Actuator motor speeds (in seconds). Enabled with a selection of floating heating, floating cooling or floating economizer.
Optional Points The first optional point is enabled if there is sufficient room on the controller. After you select the first point, the second one is enabled if there is sufficient space, and so on.

The following options are available:

  • Status_Occupied - (output energized when controller is in Occupied mode) AND/OR
  • Aux_Econ1 - (Emulates a T7300 – for controlling an external economizer ) AND/OR
  • Free1 - (Network-controlled output) AND/OR
  • Unused - (Point is unused)
Controller Type The model type
Power Frequency This field defines the line voltage that Excel 10 Controllers use and also tells LonSpec the calculation required for noise immunity. The calculation differs for 50 and 60 Hz applications
PWM Settings PWM Period time (in seconds).
  • Zero Pulse time for a 0 percent output signal (in seconds).
  • Full Pulse time for a 100percent output signal (in seconds). This value must be less than or equal to the PWM Period.

Back