Use the Unit Ventilator Miscellaneous page to set other Unit Vent application settings.
Enter all outputs, including optional outputs, to be controlled by the Unit Ventilator Controller.
Off-line or On-line
| Name | Definition |
| DLC Setpoint Bump | Upon receipt of a DLC_Shed signal over the LonWorks-Bus network, the current operating setpoint value is bumped up/down (for cool/heat modes) by this amount. Select a value from 0 through 10. |
| Override Type | Specify the type of Bypass override functions that are available from the
Wall Module's Override button. You can select one of the following options:
(no Continuous Unoccupied allowed from the button). |
| Override Priority | Set the priority scheme for the Bypass override function. You can select
one of the following options:
|
| Bypass Time | Set the time period for a bypass override event. Value ranges from 0 through 1080 minutes. Enabled if Override Type is Normal or Bypass Only. |
| Max. DaTemp SetPoint | Value ranges from 65 deg.F through 135 deg.F (18 deg.C through 57 deg.C). Enabled if you selected a discharge air temperature sensor. This setting is only used if Cascade Control is enabled. |
| Min. DaTemp | Value ranges from 0 deg.F through 60 deg.F (-18 deg.C through 16 deg.C). Enabled if you selected a discharge air temperature sensor. This setting is used in Cascade Control, and as the Low Limit alarm threshold for discharge temp. |
| Setpoint Knob Type | Select Relative (plus or minus up to 10 degrees from the current actual
setpoint set on the Zone Options page), or Absolute_Middle (the Wall Modules knob
sets the midpoint between the heat and cool current actual setpoints). You can select one of the following options:
|