HYD Zone Control
Description
To configure heating and cooling setpoints.
Purpose
Configure the heating and cooling setpoints for the Occupied, Standby, and Unoccupied
operating modes.
Mode
Configuration can be performed with the wizard Off-line or On-line.
Procedure
- Click the Zone Control button on the left pane to open the Zone
Control Configuration page.
- Enter information into available fields.
- Click Commit to save the settings or Reset to revert
to the last saved settings.
- Click Next to display the Miscellaneous Configuration page
or Back to display the Switching Levels Configuration page
.
Fields
Setpoints can range from 10 Deg.C to 35 Deg.C (50 Deg.F to 95 Deg.F).