Display the wiring diagram for the controller.
Display the wiring diagram for the controller.
Configuration can be performed with the wizard Off-line or On-line.
DI1 Window / Occupancy / Air Flow / Changeover
| Name | Definition |
| Wall Module |
|
These terminals are used to connect the LON Bus FTT-10A. The LON Bus is insensitive to polarity.
| Output 1 / Output 2 | Terminal 14/15 | Terminal 17/18 |
| Floating | 14 on =open valve | 17 on = open valve |
| 15 on = close valve | 18 on = close valve | |
| 1-stage | 14 = on/off | 17 = on/off |
| 15 = not used | 18 = not used | |
| 2-stage | 14 on = stage 1 | 17 on = stage 1 |
| 14 on + 15 on = stage 2 | 17 on + 18 on = stage 2 | |
| 3-stage | 14 on = stage 1 | 17 on = stage 1 |
| 15 on = stage 2 | 18 on = stage 2 | |
| 14 on + 15 on = stage 3 | 17 on + 18 on = stage 3 | |
| PWM | 14 = PWM | 17 = PWM |
| 15 = not used | 18 = not used | |
| Thermal | 14 = Pulse modulated | 17 = Pulse modulated |
| 15 = not used | 18 = not used |
Power Supply
24VAC: 50/60 Hz.