To configure the variables for closed loop control. PID parameters can be set separately for both heating and cooling control.
Configure the variables for closed loop control. PID parameters can be set separately for both heating and cooling control.
Configuration can be performed with the wizard Off-line or On-line.
| Name | Definition |
| PID | Cooling/Heating Proportional band This value is the temperature deviation between setpoint and space temperature, which causes the control output to modulate from 0% to 100% of full range. The variable can be set in the range 2 to 100DDC (3.6DDF to 180DDF), respectively 1.3 . 100DDC [2.3DDF to 180DDF] for P Control only. Reset Time This value is the integral reset time in the range 0 to 3200 sec. Setting the Integral constant to zero disables integral operation. Derivative Time This value is the derivative constant in the range 0 to 3200 sec. Setting the derivative constant to zero disables derivative operation. |
| Thermal Switching Band /PID Boost | Cooling/Heating Boost Temp Sets a boost band for normal PID operation and when using thermal actuators. The variables indicate a setpoint-space temperature deviation outside which the outputs are switched to full operation to act as a boost function when space temperature deviates significantly from the desired setpoint. These values also serve as a threshold for two-point switching of thermal actuators. The threshold can be set in the range 0 to 10DDC (7.2 to 180DDF). |