HYD applications can have a variable number of heating and cooling stages. The number of pipes used on the unit could be two or four. The outputs could be of staged, PWM, floating, or Thermal type. In addition the outputs can be of Change over mode.
Define the operation of the hydronic controller outputs and the type of equipment to be controlled.
Configuration can be performed with the wizard Off-line or On-line.
| Name | Definition | |||||
| Types |
Select the hardware version to be used for the controller. Each hardware version has different combinations of inputs and outputs. The software checks Type against the controller's selected application so that you cannot configure a controller for an application that it cannot perform. |
|||||
| Selection in Tool | Controller Type | Onboard Setpoint | Number of Outputs | Number of Digital In | Transceiver | |
| W7762A | W7762A | No | 2 | 1 | FTT-10 | |
| W7762B | W7762B | Yes | 2 | 1 | FTT-10 | |
Define the type of equipment (number of pipes) being controlled.
Unit has only two pipes. Selecting this system type limits the controller to control only one valve output and operate in a changeover mode. When operating in changeover mode, the controller uses only the one valve for controlling both heating and cooling. Use this configuration only when changeover operation is required.
Unit has four pipes connected, providing both heating and cooling at the same time. The controller uses one output to control heating only and one output to control cooling only (as specified in Control Outputs). |
||||||
| Control Outputs | Configures the two control outputs for the different type of
actuators and control sequences required for the application. Output 1- Mode Output triac pair connected to terminals 13/14/15 of the controller.
The output is modulated open when heat energy is needed in the space.
The output is modulated open when cool energy is needed in the space.
The output is modulated open when heat or cool energy is needed in the space.
The output is not controlled by the controller and is always off. Output 1- Type Select the type of actuator to be connected to the output.
Three-point actuator that can be commanded open or closed (terminals 14/15 and/or 17/18). The run-times for the actuator are configured on the Equipment Control tab (Output Options).
A three point actuator that can be commanded open or closed on terminals 14/15 and/or 17/18. The run-times for the actuator are configured in the Outputs tab. The Zero Energy Position (no Heat and no Cool) is the middle Position (50%). The Cool Range is 0 to 50%; the Heat Range, 50 to 100%. The Range can be reversed by selecting the Actuator Direct or Reverse Option. During the Synchronization Process, the fan is turned off.
Duty-cycled output where the 24VAC output is pulsed on/off in the duty cycle range 0% to 100%. This type drives output terminal 14 and/or 17.
Single-stage on/off output that switches terminal 14 and/or 17.
Two-stage output: Terminal 14/17 is switched for stage 1 and terminal 15/18 is switched for stage 2.
Three-stage switched output. Terminal 14/17 is switched for stage 1, terminal 15/18 is switched for stage 2. Both terminals 14+15 and/or 17+18 are switched for stage 3.
Switched on/off output for switching a 24V thermal actuator on terminal 14/17. Output 2- Mode Output triac pair connected to terminals 16/17/18 of the controller. Output 2- Type Selection options are the same as for Output 1. |
|||||