To configure energy management parameters.
To configure energy management parameters.
Configuration can be performed with the wizard Off-line or On-line.
| Name | Definition |
| Miscellaneous | Configures operator bypass and priority options. Bypass Time Define the period of time (0 to 1080 minutes) in which the controller operates to occupied setpoints after the local user has pressed the override button. Override Priority Allocate priority between local wall module operations (for example, Bypass) and commands from the building management central. Choices are:
|
| Energy Management | DLC Stpt Bump For load shedding applications, define the temporary setpoint shift to be added to the setpoint when the controller receives a Load Shedding command. By raising the setpoint during cooling operation, or reducing the setpoint during heating operation, the controller reduces the amount of heat or cool energy dissipated as a contribution to load shed algorithms. The parameter can be set in the range 0 to 10DDC (0 to 18DDF). Cool Rec Ramp, Heat Rec Ramp Define the rate at which the setpoint is reset during changes between occupancy modes to provide a form of optimum start algorithm. |