HYD Miscellaneous

Description

To configure energy management parameters.

Purpose

To configure energy management parameters.

Mode

Configuration can be performed with the wizard Off-line or On-line.

Procedure

  1. Click the Miscellaneous button on the left pane to open the Miscellaneous Configuration page.
  2. Enter information into available fields.
  3. Click Commit to save the settings or Reset to revert to the last saved settings.
  4. Click Next to display the PID Configuration page or Back to display the Zone Control Configuration page.

Fields 

Name Definition
Miscellaneous Configures operator bypass and priority options.

Bypass Time

Define the period of time (0 to 1080 minutes) in which the controller operates to occupied setpoints after the local user has pressed the override button.

Override Priority

Allocate priority between local wall module operations (for example, Bypass) and commands from the building management central. Choices are:

  • LAST WINS: Last received input takes precedence. It can be either the Bypass button or the Network signal.
  • NETWORK WINS: The Network signal always takes precedence over the Bypass button.
Energy Management DLC Stpt Bump

For load shedding applications, define the temporary setpoint shift to be added to the setpoint when the controller receives a Load Shedding command. By raising the setpoint during cooling operation, or reducing the setpoint during heating operation, the controller reduces the amount of heat or cool energy dissipated as a contribution to load shed algorithms. The parameter can be set in the range 0 to 10DDC (0 to 18DDF).

Cool Rec Ramp, Heat Rec Ramp

Define the rate at which the setpoint is reset during changes between occupancy modes to provide a form of optimum start algorithm.

Back