Use the Unit Ventilator H/C Stages page to set the minimum on/off times, Cycles/ hour, recovery ramps of a Unit Vent application for heating and cooling stages.
Define heating and cooling (h/c) stage parameters, including minimum on and off times.
Off-line or On-line
| Name | Definition |
| Min On/Off |
|
| Cycles/Hour | Cycles per hour (cph). Enter value from 2 through 12. For example, cph for conventional heating stage one is normally 3 cph. Consult your hardware installation guide for recommended values. |
| OaTemp LockOut | OA temperature lockout. OA temperature values below the cooling lockout setting disables the cooling stages. OA temperature values above the heating lockout setting disable the heating stages. |
| Ramp | Recovery ramp (degrees per hour). Enter value from 2 through 20 for cooling or 3 through 20 for heating |
| Fan Run-On Time | Enter amount of time (from 0 to 120 seconds) the fan will continue to run
after the last stage of heating or cooling has switched off. This value is only applicable during unoccupied times, and during occupied times if the Fan Control field is set to Auto_Fan. |