Display the wiring diagram for the controller.
Display the wiring diagram for the controller.
Configuration can be performed with the wizard Off-line or On-line.
DI1 Window / Occupancy / Air Flow / Changeover
| Name | Definition |
| Wall Module | Use these terminals to connect the Wall Module.
|
LON (E-Bus)
These terminals are used to connect the LON Bus FTT-10A. The LON Bus is insensitive to polarity, eliminating wiring errors during installation. Recommended wire size is level IV 22 AWG nonshielded, twisted pair, solid conductor wired.
| Output 1 / Output 2 | Terminal 14/15 | Terminal 17/18 | |
| Floating | 13 on = open valve | 15 on = open valve | |
| 14 on = close valve | 16 on = close valve | ||
| 1-stage | 13 = on/off | 15 = on/off | |
| 14 = not used | 16 = not used | ||
| 2-stage | 13 on = stage 1 | 15 on = stage 1 | |
| 13 on + 14 on = stage 2 | 15 on + 16 on = stage 2 | ||
| 3-stage | 13 on = stage 1 | 15 on = stage 1 | |
| 14 on = stage 2 | 15 on = stage 2 | ||
| 13 on + 14 on = stage 3 | 15 on + 16 on = stage 3 | ||
| PWM | 13 = PWM | 15 = PWM | |
| 14 = not used | 16 = not used | ||
| Thermal | 13 = Pulse modulated | 13 = Pulse modulated | |
| 14 = not used | 14 = not used |
Characteristics
24 VAC, 250 mA max continuous, 650 mA max surge
Fan Relays
These terminals are used to connect a Fan.
Characteristics
20 to 253 VAC, 3 A max
Power Mains In
Power Supply
W7752D and W7752E: 230 VAC + 10%, -15%, 50/60Hz
W7752F and W7752G: 115 VAC + 10%, -15%, 50/60 Hz
Power Consumption
W7752D and W7752E: 30 VA max
W7752F and W7752G: 30 VA max
Operational temperature
32 Deg.F to 122 Deg.F (0 Deg.C to 50 Deg.C)
Reheat Relay
These terminals connect a Electric Reheat.
Characteristics
20 to 200 VAC, 10 A max.