Use the Unit Ventilator Equipment Control page to select cascade control options, fan, and smoke control options.
Define Equipment Control parameters that the Excel 10 Controller uses to control the unitary equipment.
Off-line or On-line
| Name | Definition |
| Cascade Control | Cascade control modulates/stages heating/cooling to control discharge air
temperature, and uses space temperature to reset the discharge air temperature set point.
Select one of the following cascade control options:
|
| Fan Control | Select one of the following fan control options:
|
| Fan Run on Heat | Select one of the following fan control options:
|
| Smoke Control | This value determines what the controller does when a smoke alarm occurs
(either from the digital input, or via the LonWorks Bus network). Select one of the
following smoke control options:
|
| Fan Fail Time | This option is enabled if an Air Flow switch was selected. This value sets
the amount of time that must pass after closed contacts on the Air Flow switch are
detected before the controller shuts down and attempts a restart. If three fan start attempts fail to prove air flow, the controller is disabled and locked out until reset. This action allows the fan to come up to speed on start up, and prevents false air flow failure alarms. |
| Filter Setpoint | This option is enabled if an analog Filter Pressure sensor was selected. If the measured pressure exceeds this setpoint, the Dirty Filter alarm is issued. There is a built-in hysteresis of 25 percent of the Filter Press Stpt value (for the Dirty Filter alarm to return to normal). |