Use the Unit Ventilator Economizer page to configure Economizer settings.
Define Economizer functions.
Off-line or On-line
| Name | Definition |
| IAQ Sensor Setpoint | This is the Indoor Air Quality setpoint. This setting, in ppm, is compared to the current actual indoor CO2 sensor reading to determine the indoor air quality. |
| OAQ Sensor SetPoint | This is the Outdoor Air Quality setpoint. This setting, in ppm, is compared to the current actual outdoor CO or CO2 sensor reading to determine the outdoor air quality. If OAQ is poor, the economizer damper is closed to 0%. |
| Enable Type | Source for economizer enable decisions. Choose one of the following
methods to determine when to use outdoor air for cooling:
|
| OA Damper Min Pos | Minimum position of the Outdoor Damper (0 to 100%). Under normal Occupied-mode operation, the dampers are not closed below this setting. If Unoccupied, or if a Discharge Low Temperature condition exists, the dampers are closed below this setting. |
| IAQ Position | Minimum Position of Damper used when poor Indoor Air Quality conditions
exist (IAQ sensor > IAQ Setpoint, or if Digital IAQ Switch is on). Value range from 0
to 100%. NOTE: A discharge low temperature condition overrides this setting and closes the dampers to prevent equipment damage due to freezing. |
| Use Heat for IAQ | Select one of the following options:
|
| Oa Temp High Limit | This field is enabled only when Enable Type is set to Single Enth(alpy). It provides an outdoor air temperature high limit setting, above which, the economizer is disabled, regardless of the current enthalpy value. |
| Mixed Temp Setpoint (ASHRAE Cycle 3 Only) | This field is enabled only when ASHRAE Cycle III is selected in the Equipment Control Tab. |
| Ashrae Cycle | When a unit ventilator is in the occupied mode it typically follows one of
three operating cycles defined by the American Society of Heating, Refrigeration and
Air-Conditioning Engineers, Inc. (ASHRAE):
|
| Enable Setpoint/ OaEconEnTemp/ DiffEconEnTemp/ OaEnthEn |
|