Use the VFD Configuration Screen to configure the motor parameters, transmission controller parameters, and EEPROM saving option parameters.
Off-line or On-line.
| Point Name | Min. Value | Max. Value | Typical Values | Description |
| Maximum speed | 0 | 100% | 100% | Maximum motor speed The value of the maximum speed must be validated against the value of the minimum speed as follows: 0 <= minimum speed <= maximum speed <= 100 If the value is changed via the network it is not saved in the frequency converters non-volatile memory, unless bit 1 in nciEeprSave has been set to 1. |
| Minimum Speed | 0 | 100% | 0.0% | Minimum motor speed The value of the minimum speed must be validated against the value of the maximum speed as follows: 0 <= minimum speed <= maximum speed <= 100 If the value is changed via the network it is not saved in the frequency converters non-volatile memory, unless bit 0 in nciEeprSave has been set to 1. |
| Nominal Speed | 300 | 20000 | 1725 RPM 3450 RPM 1140 RPM |
Nominal motor speed in RPM. Find this value on the rating plate of the motor. Nominal motor speed in RPM. Find this value on the rating plate of the motor. This configuration property is used to provide the nominal speed of the motor in RPM. This value is necessary to determine the minimum and maximum speed for the motor, based on the configuration properties nciMinSpeed, nciMaxSpeed (entered as percent of nominal speed). If the value is changed via the network it is not saved in the frequency converters non-volatile memory, unless bit 5 in nciEeprSave has been set to 1. |
| Nominal frequency | 30 | 500 | 60 Hz 50Hz |
Nominal motor frequency This configuration property is used to provide the nominal frequency for the motor. If the value is changed via the network it is not saved in the frequency converters non-volatile memory, unless bit 4 in nciEeprSave has been set to 1. |