Use the VFD NX configuration screen to configure the motor parameters, transmission controller parameters, and EEPROM saving option parameters.
These parameters can be configured in both Off-line and On-line modes from the wizard.
| Point Name |
Min. Value |
Max. value |
Typical Values |
Description |
| Maximum Speed |
-163.84 | 163.83 | 100.0% | Maximum motor speed The value of the maximum speed must be validated against the value of the minimum speed as follows: -163.840 <= minimum speed <= maximum speed <= 163.830 |
| Minimum Speed |
-163.84 | 163.83 | 0.0% | Minimum motor speed The value of the minimum speed must be validated against the value of the maximum speed as follows: -163.84 <= minimum speed <= maximum speed <= 163.83 |
| Nominal Speed |
300 | 20000 | 1725 RPM 3450 RPM 1140 RPM |
Nominal motor speed in RPM. Find this value on the rating plate of the
motor. This configuration property is used to provide the nominal speed of the motor in RPM. This value is necessary to determine the minimum and maximum speed for the motor, based on the configuration properties nciMinSpeed, nciMaxSpeed (entered as percent of nominal speed). |
| Nominal Frequency |
30 | 320 | 60 Hz 50 Hz |
Nominal motor frequency This configuration property is used to provide the nominal frequency for the motor. |
| Acceleration Time |
0.1 | 3000.0 | 30 sec | Minimum ramp up time. Defines the acceleration time for Vacon NX |
| Deceleration Time |
0.1 | 3000.0 | 30 sec | Minimum ramp down time. Defines the deceleration time for Vacon NX |
| Default Drive Speed Scale |
-163.84 | 163.83 | 0% | Default value for nviDrvSpeedScale. It provides scaling for
nviDrvSpeedStpt. Negative values of nviDrvSpeedScale indicate reverse (anti clockwise)
direction of motor rotation. This value will be adopted at power-up and in case of not receiving any input variable within the specified Receive Heartbeat time. |