CVAHU Zone Options

Description

Heating and Cooling setpoints.

Purpose

Configure CVAHU Controller zone options such as cooling and heating setpoints (temperature settings).

Mode

Off-line or On-line.

Procedure

  1. Click the Zone Options button on the left pane to open the Zone Options Configuration page.
  2. Enter information into available fields.
  3. Click Commit to save the settings or Reset to revert to the last saved settings.
  4. Click Next to display the Miscellaneous Configuration page or Back to display the Heat-cool Configuration page.

Fields           

Name Definition
Cooling Occupied Setpoint Temperature range is 50 Deg.F – 90 Deg.F (10 Deg. C – 32 Deg.C). Thermostat reaches this temperature during Occupied times while in the cooling mode.
Cooling Standby Setpoint Temperature range is 50 Deg.F – 90 Deg.F (10 Deg.C – 32 Deg.C). Thermostat reaches this temperature during Standby times while in the cooling mode.
Cooling Unoccupied Setpoint Temperature range is 50 Deg.F – 90 Deg.F (10 Deg.C – 32 Deg.C). Thermostat reaches this temperature during Unoccupied times while in the cooling mode.
Heating Occupied Setpoint Temperature range is 50 Deg.F – 90 Deg.F (10 Deg.C – 32 Deg.C). Thermostat reaches this temperature during Occupied times while in the heating mode.
Heating Standby Setpoint Temperature range is 50 Deg.F – 90 Deg.F (10 Deg.C – 32 Deg.C). Thermostat reaches this temperature during Standby times while in the heating mode.
Heating Unoccupied Setpoint Temperature range is 50 Deg.F – 90 Deg.F (10 Deg.C – 32 Deg.C). Thermostat reaches this temperature during Unoccupied times while in the heating mode.
Min. Limit Setpoint Provides a lower limit on the allowed settings of the setpoint knob of the Wall Module. Enabled if Wall Module Setpoint is configured (Input Configuration page). Values range from -9 to 9, (Setpoint default set to OFFSET) or from 50 to 90 (Setpoint default set to ABSOLUTE_MIDDLE).
Max. Limit Setpoint Provides an upper limit on the allowed settings of the setpoint knob of the Wall Module. Enabled if Wall Module Setpoint is configured (Input tab). Values range from -9 to 9, (Setpoint default set to OFFSET) or from 50 to 90 (Setpoint default set to ABSOLUTE_MIDDLE).