Heating and Cooling setpoints.
Configure CVAHU Controller zone options such as cooling and heating setpoints (temperature settings).
Off-line or On-line.
| Name | Definition |
| Cooling Occupied Setpoint | Temperature range is 50 Deg.F 90 Deg.F (10 Deg. C 32 Deg.C). Thermostat reaches this temperature during Occupied times while in the cooling mode. |
| Cooling Standby Setpoint | Temperature range is 50 Deg.F 90 Deg.F (10 Deg.C 32 Deg.C). Thermostat reaches this temperature during Standby times while in the cooling mode. |
| Cooling Unoccupied Setpoint | Temperature range is 50 Deg.F 90 Deg.F (10 Deg.C 32 Deg.C). Thermostat reaches this temperature during Unoccupied times while in the cooling mode. |
| Heating Occupied Setpoint | Temperature range is 50 Deg.F 90 Deg.F (10 Deg.C 32 Deg.C). Thermostat reaches this temperature during Occupied times while in the heating mode. |
| Heating Standby Setpoint | Temperature range is 50 Deg.F 90 Deg.F (10 Deg.C 32 Deg.C). Thermostat reaches this temperature during Standby times while in the heating mode. |
| Heating Unoccupied Setpoint | Temperature range is 50 Deg.F 90 Deg.F (10 Deg.C 32 Deg.C). Thermostat reaches this temperature during Unoccupied times while in the heating mode. |
| Min. Limit Setpoint | Provides a lower limit on the allowed settings of the setpoint knob of the Wall Module. Enabled if Wall Module Setpoint is configured (Input Configuration page). Values range from -9 to 9, (Setpoint default set to OFFSET) or from 50 to 90 (Setpoint default set to ABSOLUTE_MIDDLE). |
| Max. Limit Setpoint | Provides an upper limit on the allowed settings of the setpoint knob of the Wall Module. Enabled if Wall Module Setpoint is configured (Input tab). Values range from -9 to 9, (Setpoint default set to OFFSET) or from 50 to 90 (Setpoint default set to ABSOLUTE_MIDDLE). |