CVAHU applications can have a variable number of heating and cooling stages. The outputs could be of staged, PWM, floating, or Analog type. In addition there is a Change over relay (Heat Pump Application)and Economizer Output. The Economizer output can be Floating, PWM, Analog, or Packaged Economizer 1. Optional points can also be selected from this selection.
Note
Packaged Economizer is selected by using "EconNonePackaged" and selecting the "AuxEcon" optional Output. This output will enable the economizer when the CVAHU is in the Occupied mode.
Enter all outputs, including optional outputs, to be controlled by the CVAHU Controller.
Off-line or On-line
- If the heating, cooling, or economizer is configured as PWM, the Period, Zero Scale, and Full Scale settings must be configured.
- If the heating, the cooling, or the economizer is configured as Floating, the Motor speed settings must be configured.
| W7750A | W7750B | W7750C | W7750B Enhanced | |
| Heating | 1 to 4 stages | 1 to 4 stages, HeatPWM or HeatingFloating | 1 to 4 stages, HeatPWM, HeatPWMRev, HeatAO, HeatAORev, or HeatingFloating | 1 to 4 stages, HeatPWM, HeatPWMRev or HeatingFloating |
| Cooling | 1 to 4 stages | 1 to 4 stages, CoolPWM or CoolingFloating | 1 to 4 stages, CoolPWM, CoolPWMRev, CoolAO, CoolAORev, or CoolingFloating | 1 to 4 stages, CoolPWM, CoolPWMRev or CoolingFloating |
| Economizer | EconNone or EconFloating | EconNone, EconPWM, or EconFloating | EconNone, EconPWM, EconPWMRev, EconAO, EconAORev, EconPackaged or EconFloating | EconNone, EconPWM, EconPWMRev, EconPackaged or EconFloating |
| Optional Points | OccStatus, AuxEcon, Free1, Free2, Free1PulseOn, Free1PulseOff. Maximum of one optional point. |
OccStatus, AuxEcon, Free1, Free2, Free1PulseOn, Free1PulseOff Maximum of three optional points. |
OccStatus, AuxEcon, Free1, Free1Rev, Free2, Free2Rev Free1PulseOn, Free1PulseOff, Free1AO, Free1AORev, Free2AO, Free2AORev, Free1Dehumidify | OccStatus, AuxEcon, Free1, Free1Rev, Free2, Free2Rev Free1PulseOn, Free1PulseOff, Free1Dehumidify. |
Note:
The optional points Free1AO, Free2AO,
Free1AORev, Free2AORev are available in W7750C Model of CVAHU only. These enumerations
must be selected to use terminals 6,7 and 8 of W7750C model. These outputs can be driven
by XL15C, but since Free1 and Free2 are digital in nature, XL15C can
only command these points to ON or OFF. Hence, these points can be driven only by digital
outputs of Xl15C loops.
| Name | Definition |
| Controller Type | Select one of the following model types:
The wizard does not allow commissioning if incorrect Model Type is selected. |
| Power Frequency | Select one of the following options:
|
| Equipment Type | Select one of the following options:
|
| Heating | Refer to table above for selecting Heating options. If you select Floating, enter the Motor Speed settings. If you select PWM, enter the PWM settings. |
| Cooling | Refer to the table above for selecting Cooling settings: If you select Floating, enter the Motor Speed settings. If you select PWM, enter the PWM settings. |
| Economizer | Refer to the table above for selecting Economizer options: If you select Floating, enter the Motor Speed settings. If you select PWM, enter the PWM settings. |
| Motor Speed | You can configure three Motor Speed settings:
If you select HeatingFloating for configuring Heating settings, Motor speed for heating is enabled. Similarly, if you select CoolingFloating or Econfloating for cooling and economizer respectively, Motor Speed for Cooling and Economizer is enabled. |
| PWM settings | PWM settings are enabled if heating, cooling, or Economizer is configured
as PWM.. It consists of Zero Scale, Full Scale, and Period values to control PWM output type. |
Note:
When selecting one of the following, the wizard assigns a digital output I/O terminal to the function.
| Name | Definition |
| Occupancy_Status | Energized if the controller is currently in Occupied mode. |
| Free1 | Network controller digital output. Follows the input signal nviFree1. Turns on when nviFree1 is on. |
| Free2 | Network controller digital output. Follows the input signal nviFree2. Turns on when nviFree2 is on |
| Free1_Pulse_On | Momentary digital output (1 Sec.). Typically used for controlling lighting systems. This output turns the lights on. Uses nviFree1 |
| Free1_Pulse_Off | Momentary digital output (1 Sec.). Typically used for controlling lighting systems. This output turns the lights off. Uses nviFree1. |
| Unused_Out | No digital output assigned. |
| Aux_Econ | Tracks occupancy (On for OCC, OFF for UNOCC). Emulates the T7300's internal economizer output signal for controlling external economizer packages. |