Other CVAHU application settings.
Define additional CVAHU Controller parameters, such as DLC setpoint bump.
Off-line or On-line.
| Name | Definition |
| IAQ CO2 Setpoint | Setting above which the Indoor Air Quality (IAQ) is deemed to be poor, and the controller enters the IAQ override mode. Values range from 0 2000 PPM (Enabled when SpaceCo2 sensor is selected). |
| DLC Setpoint Bump | Upon receipt of a DLC_Shed signal over the LonWorks network, the current operating setpoint value is bumped up/down (for cool/heat modes) by this amount. Values range from 0 10 DDF (0 - 5.56 DDK). |
| Use Wall Module | Select one of the following options:
If set to yes, the wall module setpoints are used by the controller and those set in the configuration are ignored. If set to no, the setpoint values set in the configuration are used. |
| Override Type | Specify the type of Bypass override functions that are available from the
Wall Modules Override push button. Select one of the following options
|
| Override Priority | Set the priority scheme for the Bypass override function. Options are:
This field is available only if Override Type is Normal or Bypass Only. |
| Bypass Time | Set the time period for a bypass override event. Values range from 0 through 1080 minutes. Enabled if Override Type is Normal or Bypass Only |
| Max. DaTemp Setpoint | Values range from 65 Deg.F 135 Deg.F (18.33 Deg.C 57.22 Deg.C). Enabled if a discharge air temperature sensor is selected. |
| Min. DaTemp Setpoint | Values range from 0 Deg.F 60 Deg.F (-17.78 Deg.C 15.56 Deg.C). Enabled if a discharge air temperature sensor is selected. |
| Setpoint Knob Type |
|