The minimum on/off times, Cycles/ hour, Minimum and maximum recovery ramps are set for heating and cooling stages of a CVAHU application.
Define heating and cooling (h/c) stage parameters, including minimum on and off times.
Off-line or On-line.
| Name | Definition |
| Min. On/Off | MinHeatOn enables minimum on/off time. MinHeatOff replaces set
minimum on/off times with a 30-second default. MinCoolOn enables minimum on/off time. MinCoolOff replaces set minimum on/off times with a 30-second default. |
| Cycles/Hour | Cycles per hour (cph). Enter a value from 2 through 12. For example, cph for conventional heating stage one is normally 3 cph. Consult your hardware installation guide for recommended values. |
| OAT Lockout | Outside Air (OA) temperature lockout. OA temperature values below the Cooling lockout setting disables the cooling stages. OA temperature values above the heating lockout setting disable the heating stages. |
| Min. Recov. Ramp | Minimum recovery ramp (degrees per hour). Enter a value from 2 through 20 for cooling; 3 through 20 for heating. See Excel 10 System Engineering manual, form number 74-2958, for a discussion of the recovery ramp feature of the CVAHU. |
| Min. Recov. Ramp Oa Temp | Minimum recovery Oa (outside air) temperature. Enter value from 0 through 100 for cooling or heating. See Excel 10 System Engineering manual for a discussion of the CVAHUs recovery ramp feature. |
| Max. Recov. Ramp | Maximum recovery ramp (degrees per hour). Enter a value from 6 through 20 for cooling; 8 through 20 for heating. See Excel 10 System Engineering manual for a discussion of the recovery ramp feature of the CVAHU. |
| Max. Recov. Ramp Oa Temp | Maximum recovery Oa (outside air) temperature. Enter value from 0 through 100 for cooling or heating. See Excel 10 System Engineering manual for a discussion of the recovery ramp feature of the CVAHU. |
| Fan Run On Time | Enter an amount of time (from 0 to 120 seconds) the fan will continue to run after the last stage of heating or cooling has switched off. This value is only applicable during Unoccupied times, and during Occupied times if the Fan Control field is set to AutoFan. |