Sensor type, Cascade control options, COR Mode, Fan, and Smoke control options.
Define equipment control settings.
Off-line or On-line
| Name | Definition |
| Main Sensor | Set sensor type, if any, to Space Temperature or Return Air Temperature. Return Air option is available only if a Return Air sensor is configured on the CVAHU Controller Inputs page. |
| Cascade Control | Configure cascade control. Default is No. Yes is available only if both a Discharge Air Temperature sensor and modulating heating or cooling are configured. |
| C.O.R. Fail Mode | Changeover Relay (For Heat Pump only) fail mode: Heating or Cooling. This option determines which mode (Heating or Cooling) is activated on power failure to the C.O.R. This item is available only if HeatPump was selected on the Output page. |
| Fan Control | You can select one of the following fan control options:
|
| Fan - Heating | Select one of the follwoing options:
|
| Smoke Control | This value determines what the controller does when a smoke alarm occurs
(either from the digital input, or via the LonWorks network). Select one of the follwoing
options:
|
| Fan Fail Time | Enabled when Air Flow switch is selected. This value sets the amount of time that must pass after fan start-up before the Air Flow Switch is checked. This action allows the fan to come up to speed and prevents false air flow failure alarms. |
| Filter Pressure Stpt | Filter Pressure Setpoint. Enabled if analog Filter Pressure sensor is selected. If the measured pressure exceeds this setpoint, the Dirty Filter alarm is issued. There is a built-in hysteresis of 25 percent of the Filter Press Stpt value (for the Dirty Filter alarm to return to normal). |