Economizer settings for CVAHU application.
Define the four settings for using an economizer.
Off-line or On-line
| Name | Definition |
| Enable Type | Source of the economizer enable decision for determining when to use
outdoor air for cooling. The list of available selections is:
The W7750A will have the following options only:
|
| Min. Position | Minimum position of the Outdoor Damper (0 to 100 percent). Under normal Occupied-mode operation, the dampers are not closed below this setting. If Unoccupied, or if a Discharge Low Temperature condition exists, the dampers are closed below this setting. |
| IAQ Position | Minimum Position of Damper used when poor Indoor Air Quality conditions exist (IAQ sensor>IAQ Setpoint, or if Digital IAQ Switch is on). Select a value from 0 to 100 percent. |
| Use Heat for IAQ | Enable or disable heat.
NOTE A discharge low temperature condition overrides this setting and closes the dampers to prevent equipment damage due to freezing. |
| Enable Setpoint | It defines the setpoint value for enabling the economizer |
| OA Temp High Limit | It defines the high limit for the Outside temperature |