Your Workbench PC records “before and after” TCP/IP settings made from Niagara platform connections in an ipchanges.bog file. If necessary, you can review changes from Workbench using the following procedure.
To review TCP/IP changes made from your Workbench PC
From your PC with Workbench started, do the following:
In the Nav tree, expand “My Host” and then “My File System.”
Expand “Sys Home” and then “users.”
Expand your user folder, then expand “ipchanges.bog.”
Child folders are “date-named” using the following convention:
d for example, “<yyyymmddhhmmss>d20091013141522” for 2009 Oct 13 2:15pm
Expand any folder of interest. Underneath each folder are two objects:
priorValue — TCP/IP settings that existed before this change.
newValue — TCP/IP settings that existed after this change.
Double-click a priorValue or newValue to see settings in the “Tcp Ip Host Editor” (see Figure 33).
If you have a platform connection open (to any host), you can also review the history of IP changes made from your Workbench’s TCP/IP Configuration view. Click the “” button at the bottom of the view. This shows your ipChanges.bog folder and all child change entries. Expand a change folder to see a decoded “modTime” value, for example, “13-Oct-2009 02:15 PM” (vs "d20091013141522"). Double-click a “priorValue” or “newValue” in the view
to see the settings in the “Tcp Ip Host Editor.”