The proxy extension contains configuration properties for rate calculation, and a status property for total number of pulses counted since the counter was last set or reset.

You access this view from the main menu by clicking , followed by double-clicking the NrioNetwork driver, selecting and double-clicking a module, clicking the Point Manager link, followed by clicking the hyperlink to the right end of the High Speed Counter point.
Facets determine how a point’s value displays in the station. High Speed Counter facets include a minimum, maximum, and decimal precision.

The Edit window opens when you click the Edit button.
| Property | Value | Description |
|---|---|---|
| Quantity | drop-down list, defaults to misc () | Configures the formula. |
| Unit | defaults to null | Configures the default unit. |
| max | number, defaults to Infinity | Defines the maximum high speed counter value. |
| min | number, defaults to negative Infinity | Defines the minimum high speed counter value. |
| precision | number, defaults to 1 | Defines the number of decimal places allowed. |

In addition to the standard properties (Status, Fault Cause, and Enabled), these properties support high speed counter proxy extensions.
| Property | Value | Description |
|---|---|---|
| Conversion | drop-down list, defaults to Default |
Defines how the system converts proxy extension units to parent point units.
|
| Tuning Policy Name | drop-down list, defaults to Default Policy.
|
Identifies the assigned tuning policy. During polling, the system uses such collections of rules to evaluate both write requests and the acceptability (freshness) of read requests. |
| Read Value | read-only | Reports the last value read using device facets. |
| Write Value | read-only | Reports the last value written using device facets. Applies only to writable points. |
| Poll Frequency | drop-down list, defaults to Normal |
|
| Instance | number | Defines the point’s I/O terminal address based on its hardware type. If duplicated (same instance as same hardware type, same board), the point reports a fault status. |
| Ui Type | read-only | Identifies the Nrio Universal Input point type: Resistive Input, Boolean Output, etc. |
| Output Select | drop-down list, defaults to Count |
Specifies if count total (Count) or count rate (Rate) is at the Out slot as a status numeric.
|
| Total | read-only | Reports the total number of pulses counted since the proxy extension was last set or reset. |
| Rate | read-only | Reports the calculated rate based on the Rate Calc configuration.
|
| Rate Calc Type | drop-down list |
Defines the type of rate calculation: The purpose of these calculations is to report a meaningful value.
|
| Rate Calc | additional properties |
Provides one to three properties to use in the rate calculation.
|
| Rate Calc Time | read-only | Reports the timestamp of the last rate calculation. |