The point’s display name appears at the top of the view. The screen captures show two flavors of this view. The one with three tabs opens when you edit a camera event point. The one with two tabs opens when you edit a remote module point.
There are several ways to access the views that edit points. For example:
| Property | Value | Description |
|---|---|---|
| Edit button and Facets | button and additional properties | Defines the units displayed for a point. For example, if a point is inactive or false, one may set the facet to “locked” or “normal” depending on how the system uses the point. |
| Status | read-only | Reports the status of the point. |
| Enabled | true and false |
Turns the feature on (true) and off (false). |
| Inactive State | Open and Closed |
Defines the normally inactive state of the digital input or relay output as either Open or Closed, depending on the device requirements.
|
| Properties | Value | Description |
|---|---|---|
| Facets | Edit button | Opens a window for configuring the text that appears when a camera event occurs. |
| Proxy Ext | additional properties | Expands to display proxy extension properties, which apply to camera events. Refer to Proxy Extension properties. |
| Status | read-only | Reports the status of the point. |

In addition to the standard properties (Status, Fault Cause, and Enabled), these properties support camera events.
| Property | Value | Description |
|---|---|---|
| Device Facets | additional properties | Opens an Edit window for managing facet definitions. |
| Conversion | drop-down list, defaults to Default |
Defines how the system converts proxy extension units to parent point units.
|
| Tuning Policy Name | drop-down list, defaults to Default Policy.
|
Identifies the assigned tuning policy. During polling, the system uses such collections of rules to evaluate both write requests and the acceptability (freshness) of read requests. |
| Read Value | read-only | Reports the last value read using device facets. |
| Write Value | read-only | Reports the last value written using device facets. Applies only to writable points. |
| Most Recent Event | read-only | |
| Auto Expiration | true (default) or false |
Turns this feature on and off. |
| Auto Expiration Interval | + or — hours, minutes, seconds (defaults to 45 seconds. | Configures when the event is no longer valid. |
| Point Id | read-only | Identifies the point. |
| Enable Detection On Boot | true (default) or false |
Configures the system to enable detection of this point when the station starts. |