Door view, Sensor tab

The properties on this tab configure the door sensor.
Figure 169.   Sensor tab
Image
To access this tab, under the Controller Setup menu, select Remote Devices > Remote Modules > Remote Module Setup and double-click the door device (module), click the door name, and click the Sensor tab.
Property Value Description
Closed State open or closed Defines the normal state of the designated input to match the requirements of the sensor device.
Status read-only Indicates the current state of the sensor (Locked or Unlocked), and its status {ok}, or other possibilities.
Door Held Open Limit minutes and seconds Defines the length of time that the door is allowed to be held open before the system generates an alarm.
Debounce Time None (no debounce time used), minutes and seconds (0 minutes to 59 minutes); defaults to 1 second Minimizes Door Forced alarms around the time of a validation, exit request activation, or manual door override. The intent is to prevent unwanted Door Forced alarms caused by a door bouncing open momentarily just after or just prior to an authorized entry. Two scenarios use this property.In the first scenario, a bounce after open or close occurs when a legitimate open or close is followed by slamming the door, which bounces it open momentarily causing a forced-door alarm. Setting a debounce time allows time for a bounce to occur without creating an alarm. In the second scenario, a bounced door can be quickly followed by a legitimate opening when a person attempts to open a door and the door slips out and closes momentarily before the person opens it fully. A bounce closed is not counted if it is less than the debounce time.
Door Forced Alarm Class drop-down list: Low, Medium, High, or Off. Sets the priority for a forced door alarm by choosing an appropriate alarm class:. Off cancels alarm generation.
Door Held Open Alarm Class drop-down list: Low, Medium, High, or Off. Sets the priority by choosing an appropriate alarm class. Off cancels alarm generation.
Sensor Fault Alarm Class drop-down list: Low, Medium, High, or Off. Sets the priority for a sensor fault alarm by choosing the appropriate alarm class. Off cancels alarm generation.
Sensor Input drop-down list Designates the supervised input to use for the door sensor. Select the associated check box to enable or deselect to disable the selected input.