The properties on this tab configure the door sensor.
To access this tab, under the
Controller Setup menu, select and double-click the door device (module), click the door name, and click the
Sensor tab.
| Property |
Value |
Description |
| Closed State |
open or closed |
Defines the normal state of the designated input to match the requirements of the sensor device. |
| Status |
read-only |
Indicates the current state of the sensor (Locked or Unlocked), and its status {ok}, or other possibilities. |
| Door Held Open Limit |
minutes and seconds |
Defines the length of time that the door is allowed to be held open before the system generates an alarm. |
| Debounce Time |
None (no debounce time used), minutes and seconds (0 minutes to 59 minutes); defaults to 1 second |
Minimizes Door Forced alarms around the time of a validation, exit request activation, or manual door override. The intent
is to prevent unwanted Door Forced alarms caused by a door bouncing open momentarily just after or just prior to an authorized
entry. Two scenarios use this property.In the first scenario, a bounce after open or close occurs when a legitimate open or
close is followed by slamming the door, which bounces it open momentarily causing a forced-door alarm. Setting a debounce
time allows time for a bounce to occur without creating an alarm. In the second scenario, a bounced door can be quickly followed
by a legitimate opening when a person attempts to open a door and the door slips out and closes momentarily before the person
opens it fully. A bounce closed is not counted if it is less than the debounce time.
|
| Door Forced Alarm Class |
drop-down list: Low, Medium, High, or Off. |
Sets the priority for a forced door alarm by choosing an appropriate alarm class:. Off cancels alarm generation.
|
| Door Held Open Alarm Class |
drop-down list: Low, Medium, High, or Off. |
Sets the priority by choosing an appropriate alarm class. Off cancels alarm generation.
|
| Sensor Fault Alarm Class |
drop-down list: Low, Medium, High, or Off. |
Sets the priority for a sensor fault alarm by choosing the appropriate alarm class. Off cancels alarm generation.
|
| Sensor Input |
drop-down list |
Designates the supervised input to use for the door sensor. Select the associated check box to enable or deselect to disable the selected input.
|